Control and alarm functions, 1 input programmable for different sensors, multi-voltage power supply.

 

  • <p>Configurable pid controller </p>

This controller 32x74 with dual 4-digits display is characterised by high configurability of the input and by a multi-voltage power supply from 24 to 230V AC/DC galvanically isolated and that does not require hardware selections. This translates into a single product code, which is one of the most versatile controllers in the 32x74 format. The input can be programmed for temperature sensors, resistance thermometers and thermocouples,   but also for pressure transmitters, humidity and flow sensors. The algorithm for heating-cooling PID control is optimised both for temperature control and for processes with quick transitory, like pressure control and flow control.

Functions of the ATR142 software also include Timer, with the options of delayed start of the control process or time-based control.

The outputs can be selected as command/multiple alarm modes/event. The serial communication option is RS485 with Modbus/Slave protocol.

 

Simple to use, multimedia support and traceability

For the entire range of Pixsys products we provide technical support for installation, programming and operation via our online forum and via Skype.

The interface of the PID controller ATR142ensures that the product is easy to use and that the user is also supported by auxiliaries for programming such as MEMORY-CARD or the LABSOFTVIEW programming software.

Programming tutorial videos are available on our youtube channel.

As for the entire range of PIXSYS products, thanks to the QR code the traceability of the product is guaranteed for its entire life cycle; the information and documentation online can be also be accessed by reading the QR CODE that directs your mobile device to the product's technical specifications and verifies its warranty conditions.

PID controller tutorial - English

Ordering codes

ATR142-ABC
1 Analogue Input + 2 Relays + 1 digital PNP / Supp. 24...230 V AC/DC
ATR142-ABC-T
1 Analogue Input + 1 Relay + 1 digital PNP + RS485 / Supp. 24...230 V AC/DC

Main features

Box
32x74 (front panel) x 53 mm
Power supply
24...230V AC/DC ±15% 50/60 Hz, (galvanical isolation 2500V)
Consumption
4,65 VA
Display
4 digits 0,4" green + 4 digits 0,3" red + 6 signaling leds
Operating conditions
Temperature 0-45 °C, humidity 35..95 RH% (non condensing)
Material
Box: polycarbonate ; front panel: PC ABS UL94V0 self-extinguishing
Weight
Approx. 112 g
Sealing
Front panel IP54, Box IP30, Terminal blocks IP20
Quick set-up options
Memory Card with / without battery, software LABSOFTVIEW, EASY-UP codes

Inputs

1 analogue
Res. 16 bit, selectable for TC type K, S, R, J, (automatic compensation of the cold junction 0..50 °C, ± 0,2% F.S. ± 1 Digit F.S.), thermoresistance PT100, PT500, PT1000, Ni100, PTC1K. NTC10K, (ß 3435K), process signals 0..10V(54000 points), 0/4..20mA (40000points), 0..40mV (16000 points), potentiometer 6KΩ, 150 KΩ (50000 points)
Sampling time
4,1 ms (Frequency from 4,12 Hz to 242 Hz)
1 digital input
PNP, 1/2 setpoint selection, Hold, Run Auto/man regulation, tuning start, pre-programmed cycle start (only with sensor TC, 0...10V, 0/4...20mA, 0...40mV)

Outputs

2 Relays
1 Relay 8A - 250 VAC resistive charge + 1 Relay 5A - 250 VAC resistive charge
1 digital
12 VDC - 30 mA for SSR command
Serial communication
RS485 Modbus RTU - Master/Slave
1 Auxiliary
12 VDC - 30 mA for external sensor supply

Software features

Control algorithms
ON - OFF with hysteresis, P., P.I., P.I.D., P.D. time proportioned, dead band
Tuning
manual or automatic
Data protection
Lock of command / alarm setpoint - Access to parameters by password
Alarm modes
Absolute / Threshold, band, High / Low deviation. Alarm with optional manual reset
Soft-Start
Rising gradient expressed as Degrees / Hour
Double P.I.D.
Heating / Cooling P.I.D.
Programmer function
Start / Stop, 3 steps pre-programmed cycle
Timer function
Controller function + single / double Timer
Open / Close logic
Open / Close logic for motorized valves
Setpoint
3 setpoint

User Manual - Video - Application Notes - Datasheet

Manuale - User Manual ATR142 ITA/ENG 2300.10.092-Rev.L
12/01/2017
Italiano - English
PDF
User manual ATR142 ESP 2300.10.099-Rev.H
17/01/2014
Español
PDF
User manual ATR142 FRA 2300.10.112-Rev.D
31/08/2012
français
PDF
Betriebshandbuch ATR142 DE 2300.10.192-Rev.H
31/08/2012
Deutsch
PDF
File modello/model 3D (PDF 3D - .STP)
11/09/2013
Italiano / English
PDF 3D - STEP (.stp)
AN-0036-0211 ATR142 con sensore di temperatura ad infrarossi PC151
17/01/2011
Italiano-English
JPG
AN-0045-0211 ATR142 con sensore di pressione ST-MA
17/01/2011
Italiano-English
JPG
AN-0045-2609 ATR142 con sensore di pressione ST-MA
15/05/2017
Italiano-English
JPG
Video ATR142 Memorycard
12/10/2010
English
Video Youtube
Video ATR142 Labsoftview
12/10/2010
English
Video Youtube
Certificate UL ATR121-141-142
01/02/2011
English
JPG

Installation

<p>Configurable electronic controller size and installation</p>

Size and installation

<p>Configurable electronic controller wiring plan </p>

Wiring plan