PID Temperature Controller

48x48 mm  ATR236

Control and alarm functions, Soft-start, multi-voltage power supply


 

Thermoregulator PID 48x48mm (1/16 DIN) with double 4-figure display. Single control loop.

The analogue input can be configured for different temperature sensors; relay and SSR output can be used as control or alarm. Useful extended range power supply from 24 to 230V AC/DC with galvanic isolation from the network.

The Soft-Start function allows to program a rising gradient as degrees/hour.

 

 

User friendly, multimedia support and traceability

For the entire range of Pixsys products we provide technical support for installation, programming and operation via our online forum and via Skype.

The interface of the ART236 thermoregulator ensures that the product is easy to use and that the user is also supported by auxiliaries for programming such as MEMORY-CARD or the LABSOFTVIEW programming software.

Programming tutorial videos are available on our youtube channel. As for the entire range of PIXSYS products, thanks to the QR code the traceability of the product is guaranteed for its entire life cycle; the information and documentation online can be also be accessed by reading the QR CODE that directs your mobile device to the product's technical specifications and verifies its warranty conditions.

Ordering codes

ATR236-ABC
1 Analogue input + 1 Relay + 1 digital PNP / Alim. 24..230V AC/DC

Main features

Box
48x48 (front panel) x 107 mm
Power supply
24...230V AC/DC ±15% 50/60 Hz (galvanic insulation)
Consumption
5,5 VA
Display
4 digits 0,4" green + 4 digits 0,3" red
Operating conditions
Temperature 0-45 °C, humidity 35..95 uR% (non condensing)
Material
Box: Noryl UL94V1 self-extinguishing, front panel: PC ABS UL94V0 self-extinguishing
Weight
Approx. 165 g
Sealing
Front panel: IP54 (IP65 with gasket), Box and terminal bloks: IP20
Quick set-up options
Memory Card with / without battery, software LABSOFTVIEW, EASY-UP codes

Inputs

1 Analog
Res. 16 bit, selectable for TC type K, S, R, J, (automatic compensation of the cold junction 0..50 °C, ± 0,2% F.S. ± 1 Digit F.S.), thermoresistance PT100, PT500, PT1000, Ni100, PTC1K. NTC10K, (ß 3435K)
Sampling time
4,1 ms (Frequency from 4,12 Hz to 242 Hz)

Outputs

1 Relay
Relay 5 A - 250 VAC resistive charge
1 digital
PNP 12 VDC - 30 mA max

Software features

Control algorithms
ON - OFF with hysteresis, P., P.I., P.I.D., P.D. time proportioned
Tuning
Manual or automatic
Data protection
Lock of control / alarm setpoint, Access to parameters by password
Alarm modes
Absolute / Threshold, band, high / low deviation. Alarm with optional manual reset
Auto / Man function
Command output percentage
Soft-Start
Rising gradient expressed as Degrees / Hour
Setpoint
2 setpoints

User Manual - Video - Application Notes - Datasheet

Manuale ATR236 ITA/ENG 2300.10.098-Rev.B
31/08/2012
English / Italiano
PDF
Manual ATR236 ESP 2300.10.103-Rev.A
31/08/2012
Español
PDF
Certificate UL ATR236-243
01/02/2011
English
JPG
Certificate GOST Pixsys
31/08/2012
English
JPG
File modello/model 3D (PDF 3D - .STP)
30/09/2013
Italiano / English
PDF 3D - STEP (.stp)

Installation

<p>Controller 48x48 Size and installation - Pixsys srl </p>

Size and installation

<p>Wiring plan of temperature controller 48x48  atr236</p>

Wiring plan