PRODUCTS
ATR401
Controller multisetpoint /Dual input
Controller 48x96mm (1/8 Din), Single/Double control Loop. Distinctive feature is the high configurability, resulting in a limited number of ordering codes.
Two analogue inputs are selectable for a wide range of sensors and can be related to mathematical operations like mean/difference/addition. Remote setpoint by analogue input is also available. Variable number of outputs, programmable as comman/alarm/event or analogue retransmission. RS485-ModbusRTU. Useful extended supply range 24....115/230 Volt ac/dc galvanically isolated, also between inputs/outputs.
User-friendly operation, programming tools for quick set-up (MEMORY-CARD, programming and monitoring software LABSOFTVIEW).
Ordering codes
ATR401-22ABC
2 Analogue inputs + 2 Relays 8 A + 1 SSR 12Vdc
ATR401-23ABC
2 Analogue inputs + 3 Relays 8 A + 1 SSR 12Vdc
ATR401-24ABC
2 Analogue inputs + 4 Relays 8 A + 1 SSR 12Vdc
ATR401-22ABC-T
2 Analogue inputs + 2 Relays 8 A + 1 SSR 12Vdc, 1 Output V/mA + RS485
Main features
Box
48x96 (front panel) x 123 mm
Power supply
24...230Vac/dc ±15% 50/60 Hz (with Jumper 24 - 110...230Vac)
Consumption
5,5 VA, 4W
Display
4 digits 0,4 " green + 4 digits 0,3 " red
Operating conditions
Temperature 0-45 °C, humidity 35..95 RU%
Material
Box: Noryl UL94V1 self-extinguishing, front panel: Silicon rubber V0
Weight
Approx. 350 g
Sealing
IP65 (Front panel) , IP20 (Box and Terminal bloks)
Quick set-up options
Memory Card with /without battery, software LABSOFTVIEW, EASY-UP codes
Inputs
2 Configurables
Selection TC, K, J, S, R, PT100,PT500, PT1000, Ni100, PTC1K, NTC10K
(B 3435K), 0/4..20 mA, 0..10 V, Potentiometer 6/160 Kohm, T.A.
Sampling time
Programmable up to 4,1 ms (Frequency up to 242 Hz)
1 Digital input
2...4 setpoints selection, Hold, Run, Tuning launch, automatic / manual selection
1 T.A. input
Selection T.A. 50 mA - 100 ms overlapped to AI2
Outputs
2...4 Relays
Relay 8 A - 250 Vac resistive charge
1 SSR
24 Vdc - 25 mA max
1 Analogue
Selection SSR 12Vdc - 4...20 mA or 0...10 Vdc for command or retransmission PV/SPV
Serial communication
RS485 Modbus RTU - Slave
Software features
Control algorithms
ON - OFF with hysteresis, P., P.I., P.I.D., P.D. time proportioned
Tuning
Manual or automatic
Data protection
Lock of control / alarm setpoint, Access to parameters by password
Alarm modes
Absolute / Threshold, band, High / Low deviation. Alarm with optional manual reset. Loop Break Alarm function
Remote setpoint
Comman setpoint corresponding to AI2 (4...20 mA / 0...10 V)
Double P.I.D.
Heating / Cooling P.I.D.
Double input mode
AI1 and AI2 inputs correlation as mean, difference or addition of process values
Soft-Start
Rising gradient expressed as Degrees / Hour
Open / Close logic
Open / Close logic for motorized valves
_last update 22/02/2012