PRODUCTS

MCM260

I/O expansion module for PLC/HMI

These modules are conceived for acquisition and management of remote I/O and for expansion of networks relying on PLCs, PCs or HMIs. Multi-point RS485 for ModbusRTU or alterntively a CANbus forCANopen allow the integration both with Pixsys devices as well as instrumentation of other manufacturers (including EDS files for CANbus).

Five different versions offer various combinations of both digital and analogue I/O.


Ordering codes

MCM260-1AD
16 Digital outputs 700mA
MCM260-2AD
16 Digital outputs PNP
MCM260-3AD
8 Digital outputs 700mA + 8 Digital inputs PNP
MCM260-4AD
8 Relay outputs 5A + 8 Digital inputs PNP
MCM260-5AD
4 Universal analogue inputs + 2 Analogue outputs V/mA

Main features

Box
Standard DIN43880 90 x 71 x 58 (H) mm with DIN RAIL mounting fitting EN50022
Power supply
12...24Vac/Vdc ±15% 50/60 Hz
Consumption
2W ... 4W
Operating conditions
Temperature 0-45 °C, humidity 35..95 uR%
Material
Noryl V0
Weight
Approx. 255 gr.
Sealing
IP20 Box

Inputs

Analogue 16 bit
4 Selectable for TC, K, J, S, R, PT100, PT500, PT1000, Ni100, PTC, NTC, 0/4..20 mA, 0/1..10 V, Potentiometer FS 6/160Kohm (code -5AD)
Analogue 10bit
2 Inputs 0...10Volt / 500 Hz (overlapped to 2 digital inputs on codes -2AD/-3AD/-4AD)
Digital
8 Inputs PNP (codes -3AD/-4AD) 16 inputs PNP (code -2AD)
Counters / Encoder
2 Input for counters of 2Khz or 1 input for incremental Encoder at 10Khz (overlapped to 2 digital inputs on codes -2AD/-3AD/-4AD)

Outputs

Digital
16 Digital 700mA (code -1AD), 8 Digital 700mA (code -3AD)
Analogue
2 selectable as 0...10Volt or 4...20mA 12 Bit (code -5AD)
Relays
8 relays 5A resistive charge (code -4AD)
Communication ports
1 serial RS485 on extractable terminal + 1 Bus CANopen with EDS file for net configuration

Software features

HMI - Operator interface
TD240 / TD320 / TD640 / TD800 / SCADA for control or supervision of iany ndustrial plants
Protocol for RS485
Modbus RTU Slave up to 57600 Baud
_last update 22/02/2012