MCM260

I/O Module, PLC/HMI expansion


 

These expansion modules are an ideal solution for the acquisition and management of remote I/Os for expanding base architecture in applications that already include PLCs, PCs, or operator terminals. The multipoint serial RS485 with Modbus RTU protocol and CANopen high-speed bus, allow easy integration (including with EDS files for CAN bus) with the components of Pixsys and other manufacturers.


There are 5 product codes available for solutions that offer different input and output combinations, both analogue and digital or relay.

PLC/HMI expansion tutorial - English

Main features

Box
Standard DIN43880 90 x 71 x 58 (H) mm with DIN RAIL mounting fitting EN50022
Power supply
12...24V AC/DC ± 15% 50/60 Hz
Power Consumption
2..4VA
Operating conditions
Temperature 0-45 °C, humidity 35..95 uR% (non condensing)
Material
Noryl V0
Weight
Approx. 255 g
Sealing
Box: IP20
Wiring
Extractable terminal blocks
Bus Protocol
Modbus RTU slave (RS485 max. 57600 Baud) or CAN Open (max 1 Mbit/sec) with EDS file for net configuration
HMI - Operator interface
PL250/ PL260/ TD240/ TD320/ TD430/ TD700/ TD750/ TD850/ TD900/ SCADA for control or supervision of any industrial plants

Technical feature

ORDERING CODESMCM260-1ADMCM260-2ADMCM260-3ADMCM260-4ADMCM260-5AD
Power supply 12..24Vdc±15% 12..24Vac/dc ±15%  12..24Vdc ±15%  12..24Vac/dc ±15%  12..24Vdc ±15%
Digital input  - 16 PNP 8 PNP 8 PNP -
Encoder input   1 Enc. 10KHz 1 Enc. 10KHz 1 Enc. 10KHz -
Counter input - 2 Count. 2KHz 2 Count. 2KHz 2 Count. 2KHz  -
Analogue input - 2 over D.I. 2/3 (Res. 10 bit, 5000 points) only 0..10 V - 2 over D.I. 2/3 (Res. 10 bit, 5000 points) only 0..10 V 4 (Res. 16 bit) selectable: TC type K,S,R,J (automatic compensation of the cold unction 0..50 °C, ±0,2% F.S. ±1 Digit F.S.), thermoresistances PT100, PT500, PT1000, Ni100, PTC1K, NTC10K, (β 3435K), process signals 0..10 V (54000 points), 0/4..20mA (40000 points), 0..60 mV (16000 points), potentiometer 6 KΩ, 150 KΩ (50000 points)
Digital output 16(700 mA max. 4A Tot.) - 8 (700 mA max. 4A Tot.) - -
Relays - - - 8,5A res. Load -
Analogue output - - - - 2 (Res 12 bit) selectable: 4..20 mA (6000 points ± 0,2% F.S.) or 0..10 V DC (9500 points ± 0,2% F.S.)
Galvanical isolation From supply to serial Bus  From supply to serial bus  From supply to serial bus  From supply to serial bus  From supply to analogue input / output to serial Bus 

 

 

 

User Manual - Video - Application Notes - Datasheet

Manuale MCM260 2300.10.070-RevE
04/09/2012
Italiano
PDF
User Manual MCM260 2300.10.078-RevE
04/09/2012
English
PDF
Video TD430-MCM260
29/08/2012
English - Italiano
Video Youtube
Certificate UL MCM260
01/02/2011
English
JPG

Installation

Size and installation