PRODUCTS

TCK  EASY-UP

Diameter 6mm

Thermocouple is basically an electric circuit made of two dissimilar metallic conductors welded on one extremity. For the principle known as Seebeck effect, whenever there's a difference of temperature between hot junction (welding point) and cold junction (other extremity) of conductors, an electromotive force is generated, depending on the metals type. To measure the temperature using a thermocouple, the temperature of cold junction must be already known, so that the electromotive force depends only on hot junction.

Type K thermocouple is made of a positive conductor Nichel-Chromium and a negative conductor Nichel-Aluminium. Suitable for high temperature ranges in oxidant atmospheres.


Ordering codes

2000.90.537
BLI-TCK-6X100-A316-0000-3 m TTS cable
2000.90.068
BLI-TCK-6X100-I600-0000-3 m TTS cable
2000.90.538
BLI-TCK-6X200-A316-0000-5 m TTS cable
2000.90.025
BLI-TCK-6X200-I600-0000-5 m TTS cable

Sliding junction ordering codes

2000.30.003
Sliding junction Ø 6x1/8" GAS
2000.30.006
Sliding junction Ø 6x1/4" GAS
2000.30.027
Sliding junction Ø 6x1/4" NPT
2000.30.009
Sliding junction Ø 6x1/2" GAS

Main features

Sheath diameter
6mm
Immersion material
Steel AISI 304 / AISI 316 / Inconel 600
Internal insulation
MgO Magnesium oxide > 20Mohm @ 25°C (500Vdc)
Sensor
Thermocouple K (NiCr-NiAl / Cromel-Alumen), Wire 1,02mm, insulated junction
GSC cable
Silicon rubber, operating temperature -40 ... 250°C
TTS cable
Glass fiber, operating temperature -200 ... 500°C
Sealing
40mm bend proof spring between cable and stem
Response time
1,9 seconds (BS 1904/1984/CEI60751)
Operating range
A316 -100..+600°C / I600 -100..+800°C.
Easy-Up code
Code 2352 (-100..+600°C - A316) , Code2351 (-100..+800°C - I600)
_last update 22/02/2012