MCM260X

Expansion module Modbus RTU - CANopen


 

  • <p>Expansion module MCM260 Pixsys srl </p>

Expansion modules are a good solution for logging and management of remote I/Os and for expanding the basic structure in applications that already include PLCs, PCs or operator terminals. The RS485 serial port with Modbus/RTU protocol and the CANopen high-speed bus allow easy integration (including EDS files for CANopen) into devices from Pixsys and other manufacturers. 

The devices are included in the Pixsys catalogue, inside the LogicLab development tool for quick integration into projects to be developed. 

There are 6 part numbers available for solutions providing different combinations of analogue, digital or relay inputs and outputs.

A special parameter configuration allows to repeat the operation of the previous MCM260, ensuring full compatibility between the two series.

Addressing and setting of communication parameters are possible by using a 4-digit display and  function keys under the front panel, or by NFC through MyPixsys App, like the latest Pixsys devices. 

 

User friendly multimedia support and traceability

For the full range of Pixsys products we provide technical support for installation, programming and operation on our online forum and Skype.

Tutorial programming videos are available on our YouTube channel.

As for the whole range of PIXSYS products, thanks to the QR code,traceability of the product is ensured throughout its full life; the information and documentation online may also be accessed by reading the QR CODE directing your mobile device to the technical product specifications and to the warranty conditions.

 

PLC/HMI expansion tutorial - English

Main features

Box
Standard DIN43880 90 x 71 x 58 (H) mm with DIN RAIL mounting fitting EN50022
Power supply
12..24V AC/DC ± 15% 50/60 Hz
Power Consumption
2..4VA
Operating conditions
Temperature 0..500°C, humidity 35..95 uR% (non condensing)
Material
Noryl V0
Weight
Approx. 255 g
Sealing
Box: IP30
Wiring
Extractable terminal blocks
Bus Protocol
Modbus RTU slave (RS485 max. 115200 Baud) or CAN Open (max 1 Mbit/sec) with EDS file for net configuration
HMI - Operator interface
TD410/ TD710/ TD810 /TD820/ TD750/ TD850/ TD900-910-920/ third-party SCADA for control or supervision of any industrial plants

Technical feature

ORDERING CODESMCM260X-1ADMCM260X-2ADMCM260X-3ADMCM260X-4ADMCM260X-5ADMCM260X-9AD
Power supply12..24Vdc±15%12..24Vdc ±15% 12..24Vdc ±15% 12..24Vac/Vdc ±15%

 12..24Vdc

±15%

 12..24Vdc

±15%

Digital input -16 PNP 12-24Vdc8 PNP 12-24Vdc8 PNP 12-24Vdc-16 PNP 12-24Vdc overlapped to the  digital outputs
Encoder input  3 Enc./count. 32 bit - max. 80KHz3 Enc./count. 32 bit - max. 80KHz3 Enc./count. 32 bit - max. 80KHz-4 Enc./count. 32 bit - max. 80KHz
Analogue input-2 inputs 0..10V overlapped to the digital inputs. Resolution 45000 counts.-2 inputs 0..10V overlapped to the digital inputs. Resolution 45000 counts.4 (Res. 16 bit) selectable: TC type K,S,R,J,T,E,N,B (automatic compensation of the cold junction 0..50 °C, ±0,2% F.S. ±1 Digit F.S.), thermoresistances PT100, PT500, PT1000, Ni100, PTC1K, NTC10K, (β 3435K), process signals 0..10 V (54000 points), 0/4..20mA (40000 points), 0..60 mV (16000 points), 0..10V, 0..5V, potentiometer 0..150 KΩ (50000 points)4 (Res. 16 bit) selectable: TC type K,S,R,J,T,E,N,B (automatic compensation of the cold unction 0..50 °C, ±0,2% F.S. ±1 Digit F.S.), thermoresistances PT100, PT500, PT1000, Ni100, PTC1K, NTC10K, (β 3435K), process signals 0..10 V (54000 points), 0/4..20mA (40000 points), 0..60 mV (16000 points),0..10V, 0..5V, potentiometer 0..150 KΩ (50000 points)
Digital output16(700 mA max. 3A Tot.)-8 (700 mA max. 3A Tot.)--16 (700 mA max. 2A Tot. for group of 8 outputs)
Relays---8 relais output with a single common- 
Analogue output----2 (Res 16 bit) selectable: 4..20 mA or 0..10 Vdc2 (Res 16 bit) selectable: 4..20 mA or 0..10 Vdc
Galvanical isolationFrom supply to serial Bus From supply to serial bus From supply to serial bus From supply to serial bus From supply to analogue input / output to serial Bus From supply to analogue input / output to serial Bus 

 

 

 

User Manual - Video - Application Notes - Datasheet

User manual MCM260X 2300.10.265 revE
23/10/2019
English / Italian
PDF
File modello/model 3D (PDF 3D - .STP)
10/10/2018
English Italian
PDF 3D - STEP (.stp)
MCM260X EDS Files
12/03/2019
English
EDS Files (.eds)
File modello/model .DXF
20/06/2019
English Italian
.dxf