2000.35.016/17
DIN rail mounted signal converter - RFid / NFC
The signal transmitter from DIN rail converts a signal received through probes PT100, Ni100 (with 2-, 3- and 4-wire connections), thermocouples or process signals (0/4..20mA, 0..10V) into a normalised current signal 4..20 mA (2-wire power loop). The characteristics of these converters ensure high precision on the reading scale with 16 bit conversion and the possibility to rescale the analogue output 4..20 mA according to the input set. The RTD/TC input is galvanically isolated at 2500 V from the analogue output, which ensure safer cables in environment where they may be disturbed or in cases where there different voltages in the same system.
Forum updates (technical support)
Ordering codes
2000.35.016
RTD (PT100/NI100)+ TC (K-S-R-J-T-N-B-E) to 4..20 mA Loop Powered - isolated version
2000.35.017
0..20 mA / 4..20 mA / 0..10V / resistance to 4..20 mA loop powered - isolated version
Main features
Box
DIN43880, Din rail mounted 1 module
Current output
4..20 mA Loop Power (2 wires), operating range 6-32 V DC
Connection
Screw pins
Operating temperature
-40+85 °C, humidity 30..90 RH% (non condensing)
Material
Box: polycarbonate V0; Front panel: silicon V0
Weight
Approx. 30 g
Set-up
Programmable by RFid (NFC)
Technical data
Selectable analogue input
PT100 (2/3/4 wires), Ni100, TC K-S-R-J-T-N-B-E, 0..20 mA, 4..20 mA, 0..10V, 0..4000Ω
Digital Input
Button for calibration functions
Isolation
Galvanic isolation input/output
Output resolution
2 µA
Failure output
selectable 21,5 mA or 3,8 mA
Current output protection
30 mA approx.
Rejection
50-60 Hz
Sampling/response time
300ms / approx. 600 ms
Cable resistance
Max 20Ω
Temperature coefficient
< 100 ppm