The PTA-T-1PH-xxx-LP models are isolated, non-contact TRMS AC/DC or bipolar DC current transducers.
The main specifications of the devices are as follows:
- Direct and alternating current transducer galvanically insulated from the measuring circuit
- Measurement principle: Hall Effect
- Possibility to measure the direct and alternating component of TRMS current
- No shunt, no wasted power of primary current circuit and no dissipation.
- Unipolar or bipolar measurement.
- High measurement accuracy.
- Two DIP-Switches selectable ranges.
- Damping filter availability to improve stable reading.
- Suitable for batteries, battery chargers, solar panels, power units and generic dc loads.
- Compact dimensions
- Dimensions41 x 44 x 26mm or 96,5 x 68 x 26mm
- MaterialPA6, Red color
- Weight47gr
- SealingBox and terminal blocks: IP20
- Operating conditionsTemperature: -20..+70°C, Humidity: 10 ÷ 90% non condensing, Altitude: 2000m a.s.l. max
- Hole diameter12,3 or 20,8mm
- MountingFree-standing or on IEC EN60715 DIN rail with accessories included
- ConnectionsRemovable screw terminals, 5,08 mm pitch, for cables up to 2.5 mm².
Through hole
| ORDERING CODES | PTA-T-1PH-050-VT | PTA-T-1PH-300-VT |
|---|---|---|
| Power supply | On screw terminals + and - | |
| Tension | 9..28Vdc | |
| Max absorption | 22mA (with no load) | |
| INPUT | On through hole 12.3mm diameter | On through hole 20.8 mm diameter |
| Type of measure | AC/DC True RMS or Bipolar DC | |
| Peak factor | 1,3 | |
| Pass-band | 1kHz | |
| Over-current | 300 A continuous | |
| Current-carrying capacity | AC/DC True RMS: 0 – 25A or 0 – 50A; DC Bipolar: -25/+25A or -50/+50A | AC/DC True RMS: 0 – 150A or 0 – 300A; DC Bipolar: -150/+150A or -300/+300A |
| OUTPUT | On screw terminals Vout and GND | |
| Type | 4..20mA Minimum load R = 600Ω. | |
| Protections | Reversal polarity protection and over-voltage protection | |
| Resolution | 10bit (1000pts) | |
| EMI error | <1% | |
| Temperature coeff. | < 200 ppm/°C | |
| Measure hysteresis | 0.3% of full-scale | |
| Response time | with ‘Fast’ filter 500 ms, with ‘Slow’ filter 1000 ms. | |
| Type | Under 2% of full-scale: 1% of full-scale at 50/60Hz, 23°C; Over 2% of full-scale: 0,5% of full-scale at 50/60Hz, 23°C | |
| Over voltage category | Bare conductor: CAT.III 300V; Insulated conductor: CAT.III 600V | |