2000.35.013 2000.35.014
Signal converter from Current transformer to 4...20mA / RS485
The 2000.35.013 is a direct and alternating current transformer, galvanically isolated from the measuring circuit. The device is functionally and aesthetically similar to a standard active TA, but is able to measure the TRMS direct and alternating component.
The transformer is powered in loop with current 4-20mA and thus does not require a direct power supply. It is the first Hall loop-powered transformer with a precision of 0.5% on the market.
On the version with serial output RS485 Modbus (2000.35.014) and analogue output 0-10V, the span and zero can be freely configured and a Modbus address assigned; it is easy to configure using the library in the development tools of Pixsys HMIs.
Ordering codes
2000.35.013
Current transformer > 4...20mA Loop Powered
2000.35.014
Current transformer > RS485 Modbus /slave + 0...10Volt
Main features
Dimensions
46,1 x 63 x 26,4 mm (terminal block excluded)
Power supply
Loop-powered (2 wires) operating range 11-30 Vdc
12...35Vdc on version with RS485
Connection
screw terminal 5,08mm
Fixing
DIN-rail (horizontal/vertical)
Operating conditions
Temperature -40+85 °C, humidity 10..90 uR% (non condensing)
Material
Gray PBT, epoxy resin filling
Weight
Approx. 72 g
Dip-switch
2 / 8 poles
Conformity standards
CE, EN 61000-6-4, EN 61000-6-2, EN 61010-1
Technical data
Measure type
TRMS
Resolution and accuracy
12 Bit - 0,5% full scale
Capacity
50 Arms or 25 Arms selectable by Dip-Switch, bipolar (+/-50A dc or +/-25A dc)
Output
4...20mA or 0...10Volt + RS485
Passband -3dB
DC or 20...2000Hz
Response speed
1000 ms
Isolation
3 Kv on bare cable
Overload
2 kA impulsive, 300 continuous
Crest factor
2
Hysteresis on measured value
0,15% full scale